Monday, February 27, 2017

Calculating Floor Area (Electrical)

The general lighting load for a dwelling is based on the square footage of the dwelling. Here is how this is done.

First Floor Area

To estimate the total load for a dwelling, the occupied floor area of the dwelling must be calculated. Note in the residence plans that the first floor area has an irregular shape. In this case, the simplest method of calculating the occupied floor area is to determine the total floor area using the outside dimensions of the dwelling. Then, the areas of the following spaces are subtracted from the total area: open porches, garages, or other unfinished or unused spaces if they are not adaptable for future use, NEC 220.12.

Many open porches, terraces, patios, and similar areas are commonly used as recreation and entertainment areas. Adequate lighting and receptacle outlets should be provided for these areas.

For practicality, we had chosen to round up dimensions for the determining of total square footage and to round down dimensions for those areas (garage, porch, and portions of the inset at the front of the house) not to be included in the computation of the general lighting load. This produces a slightly larger result as opposed to being on the conservative side. Don’t be miserly with your measurements; rather, be generous. Figure 3-2 shows the procedure for calculating the total square footage of this residence.

Basement Area

Although the NEC in 220.12 tells us that unused or unfinished spaces not adaptable for future use do not have to be included in calculating the square footage of a dwelling, it makes sense to include some of these spaces.

Nearly all basements in homes today certainly could be considered as being adaptable for future use. A crawl space and most attics would not normally be considered as being adaptable for future use. This is a judgment call based on a close examination of the Plans and Specifications. In this residence, more than half of the total basement area is finished off as a recreation room, which certainly is considered a living area. The workshop area also is intended to be used.

To simplify the calculation for this residence, we will consider the entire basement as usable space and figure the basement square footage area as being the same as the area of the first floor.

The combined occupied area of the dwelling is found by adding the first floor and basement areas together:

First Floor     1616 ft2 (149 m2)
Basement     1616 ft2 (149 m2)
Total              3232 ft2 (298 m2)

Sunday, February 26, 2017

Calculating Residential Loads (Basics)

When wiring a house, it is all but impossible to know which appliances, lighting, heating, and other loads will be turned on at the same time. Different families lead different lifestyles. There is tremendous diversity. There is a big difference between “connected load” and “actual load.” Who knows what will be plugged into a wall receptacle, now or in the future? It’s a guess at best. Over the years, the NEC has developed procedures for calculating loads in typical one- and two-family homes.

The rules for doing the calculations are found in Article 220. For lighting and receptacles, the computations are based on volt-amperes per square foot. For the small-appliance circuits in kitchens and dining rooms, the basis is 1500 volt-amperes per circuit. For large appliances such as dryers, electric ranges, ovens, cooktops, water heaters, air conditioners, heat pumps, and so on, which are not all used continuously or at the same time, there are demand factors to be used in the calculations. Following the requirements in the NEC, the various calculations roll together in steps that result in the proper sizing of branch circuits, feeders, and service equipment.

Inch-pounds versus Metrics When Calculating Loads

Converting inch-pound measurements to metric measurements and vice versa results in odd fractional results. Adding further to this problem are the values rounded off when the NEC Code-Making Panels did the metric conversions. When square feet are converted to square meters and the unit loads are calculated for each, the end results are different—close, but nevertheless different. To show both calculations would be confusing as well as space consuming. Many of the measurements in this text are shown in both inch-pound units and metric units. Load calculations throughout this text use inch-pound values only, which is in agreement with the Examples given in Annex D of the 2011 NEC.

Basics of Wire and Loading

The NEC establishes some very important fundamentals that weave their way through the decisionmaking process for an electrical installation. They are presented here in brief form, and are covered in detail as required throughout this text.

The NEC defines a branch circuit as The circuit conductors between the final overcurrent device protecting the circuit and the outlet(s).* See Figure 3-1. In the residence discussed in this text, the wiring to wall outlets, the dryer, the range, and so on, are all examples of a branch circuit.

The NEC defines a feeder as All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device.* In the residence discussed in this text, the wiring between Main Panel A and Subpanel B is a feeder.

The ampacity (current-carrying capacity) of a conductor must not be less than the rating of the overcurrent device protecting that conductor, NEC 210.19 and NEC 210.20. A common exception to this is a motor branch circuit, where it is quite common to have overcurrent devices (fuses or breakers) sized larger than the ampacity of the conductor. Motors and motor circuits are covered specifically in NEC Article 430. The ampere rating of the branchcircuit overcurrent protective device (fuse or circuit breaker) determines the rating of the branch circuit. For example, if a 20-ampere conductor is protected by a 15-ampere fuse, the circuit is considered to be a 15-ampere branch circuit, NEC 210.3.

Standard branch circuits that serve more than one receptacle outlet or more than one lighting outlet are rated 15, 20, 30, 40, and 50 amperes. A branch circuit that supplies an individual load can be of any ampere rating, NEC 210.3.

If the ampacity of the conductor does not match up with a standard rating of a fuse or breaker, the next higher standard size overcurrent device may be used, provided the overcurrent device does not exceed 800 amperes, NEC 240.4(B). This deviation is not permitted if the circuit supplies receptacles where “plug-connected” appliances, and so on, could be used, because too many “plug-in” loads could result in an overload condition, NEC 240.4(B)(1). You may go to the next standard size overcurrent device only when the circuit supplies other than receptacles for cord-and-plug-connected portable loads.

For instance, when a conductor having an allowable ampacity of 25 amperes [see NEC Table 310.15(B) (16 )] 14 AWG Type THHN is derated to 70%:

25 x 0.70 = 17.5 amperes

It is permitted to use a 20-ampere overcurrent device if the circuit supplies only fixed lighting outlets or other fixed loads.

If the previous example were to supply receptacle outlets, then the rating of the overcurrent device would have to be dropped to 15 amperes; otherwise it is possible to overload the conductors by plugging in more load than the conductors can safely carry.

The allowable ampacity of conductors commonly used in residential occupancies is found in NEC Table 310.15(B)(16). This includes Type NM cable. It is required to be manufactured with 90°C insulated conductors. Typically, the insulation is Type THHN. As a result, the cable is limited to use in dry locations. See NEC 334.10(A)(1). NEC 334.80 allows the 90°C ampacity to be used for derating purposes so long as the final ampacity is selected from the 60°C column of NEC Table 310.15(B)(16).

The ampacities in Table 310.15(B)(16) are subject to correction factors that must be applied if high ambient temperatures are encountered—for example, in attics; see NEC Table 310.15(B)(2)(a).

Conductor ampacities are also subject to a derating factor if more than three current-carrying conductors are installed in a single raceway or cable; see NEC Table 310.15(B)(3)(a). See Chapter 18 for complete coverage of correction and derating factors.

Most general-use receptacle outlets in a residence are included in the general lighting load calculations, NEC220.14(J).

Receptacle outlets connected to the 20-ampere small-appliance branch circuits in the kitchen, dining room, laundry, and workshop are not considered part of the general lighting load. Additional load values must be added into the calculations for these receptacle outlets. This is discussed later in this text.

The minimum lighting load for dwellings is 3 volt-amperes per square foot. See NEC 220.12 and Table 220.12.

Continuous Loads

The NEC defines continuous load in Article 100 as a load where the maximum current is expected to continue for three hours or more.* Continuous loads shall not exceed 80% of the rating of the branch circuit. General lighting outlets and receptacle outlets in residences are not considered to be continuous loads.

Certain loads in homes are considered to be continuous and must be treated accordingly. Examples are electric water heaters (422.13), central electric heating [424.3(B)], snow-melting cables (426.4), and airconditioning equipment (440.32). For these loads, the branch-circuit rating, the conductors, and the overcurrent device shall not be less than 125% of the rating of the equipment. Mathematically, sizing the conductors and overcurrent device at 125% of the load is the same as loading the conductors and overcurrent device to 80%.

For example, an electric furnace with a nameplate rating of 40 amperes would require the supply conductors and overcurrent protection to be not less than

40 x 1.25 = 50 amperes

Sunday, March 13, 2016

IEC-French Standard Typical Residential from NFC 15-100 Requirements

IEC French Standard Typical Wiring diagram and electrical installations required by NFC 15-100

SUPPLY
Usually single phase (230 V / 50 Hz). Earth is usually local (TT system). The protective conductor is mandatory in every circuit. An AD fuse is installed on the phase in conjunction with the main circuit breaker.

METER
A single kW/h meter is supplied. If an optional off-peak power fare is subscribed, a 2-fares meter with pilot-line switching is installed.

MAIN CIRCUIT-BREAKER
This device has 3 functions:
- Acts as the main switch of the installation
- Limits the current consumption to a pre-settled level of the contract with electricity supplier
- Provides protection against indirect contact through a residual current protection (type S, 500 mA).

LIGHTNING PROTECTION
The installations supplied by an overhead electric Iine and located in high risk lightning areas have to be protected by a Surge Protective Device (SPD) installed downstream of the main residual current circuit breaker. The Surge Protective Device has to be connected to the main earth terminal of the consumer unit.

CONSUMERS DISTRIBUTION BOARD
All the protection and control functions of the electrical installation are located in the main household trunking (called GTL). The power distribution panel board and the communication panel
board are located in the GTL.

POWER DISTRIBUTION PANEL BOARD
This panel board concentrates all the control and protection functions of the electrical installation. The protection against overcurrent (short circuit and overload) is provided by circuit-breakers or fuses. All the circuits have to be protected by a 30 mA RCD in order to provide the complementary protection against the direct contacts. Other devices could be located in the panel board as:
- Time switches and time delay relays
- Bell transformer
- Power relays (heating, etc)
- Latching relays for lighting
- Signalling lamps
- Daylight/dusk switches
- Dimmers
- Land-shedding relays
- Off-peak power relays
- Buzzer or bell.

CIRCUIT PROTECTION AGAINST OVERCURRENT
Each circuit has to be protected against overcurrent at its origin. The overcurrent protection device shall ensure the simultaneous breaking of both phase and neutral conductors. The protection device should be a miniature circuit breakers or a fuse cartridge.

SPECIALIZED CIRCUITS
Some appliances (e.g. washing machine, freezer, dishwasher, etc) should be supplied by a dedicated circuit having the appropriate cross sectional area and overcurrent and RCD protection. They will be connected either via a socket or via a cable outlet box (e.g. oven, cooking plate, water-heater).

SOCKET OUTLETS
The socket outlet circuits are installed in a star configuration. The maximum number of socketoutlets is 8 on a 2.5 mm2 circuit and 5 on a 1.5 mm2 circuit. Socket outlets are of the earthed type 2P+E. Shutters are mandatory for all type of socket-outlets up to 32 A.
PLUGS
They can be 2P or 2P+E type. The flat bodied 2P type should have sleeved pins. Specific 20 A and 32 A plugs are also available for high power circuits.

LIGHTING POINTS
The lighting circuits are installed in a star configuration. A maximum of 8 points per circuit is allowed, each controlled by switches or dimmers. Multiple-point control of lighting is usually achieved by latching relays and push-buttons. The use of time-lag switches for the light control in public areas is also recommended.

EARTHING
The earthing terminal is usually provided by a closed loop foundation earth electrode. Supplementary bonding of metal fittings in bathroom, kitchens, etc., is mandatory.

CABLING
Most domestic wiring is run either in plastic surface mounted trunking or in plastic flushed-in conduit systems. Generally PVC insulated solid copper conductors are used in fixed wiring. Concerning the surface-mounted trunking systems, the protection against the external influences has to be ensured throughout the entire length of the circuit.

ELECTRICAL ACCESSORY INSTALLATION
Switches, sockets, etc., should be installed in a flush or surface mounted box or in an especially designed trunking system. All the accessories have to be screw fitted.

OUTDOOR CIRCUITS
The use of a 30 mA RCD protection is mandatory for the protection of the domestic outdoor circuits. Outdoor sockets should be at least IP 44.

BATHROOMS
Specific rules apply for circuits in bathrooms.

COMMUNICATION BOARD
In the domestic installation a communication board is installed in the main household trunking (GTL). It is the central part of the communication network of the dwelling. Each room of the dwelling is supplied by a twisted pair cable originating from the communication board and terminating with an RJ 45 socket. This communication network is able to provide different services such as telephone, Ethernet and TV.

Saturday, March 12, 2016

British Standard BS7671

BS 7671


BS7671 free pdf link : http://bit.ly/1QNIdGf

British Standard BS 7671"Requirements for Electrical Installations. IET Wiring Regulations.", informally called The "Regs" (wiring regulations), is the national standard in the United Kingdom for electrical installation and the safety of electrical wiring in domestic, commercial, industrial, and other buildings. In general, BS 7671 applies to circuits supplied at nominal voltages up to and including 1000 volts AC or 1500 volts DC. The standard therefore covers the 230 volt 50 Hz AC mains supply used in the UK for houses, offices, and commerce.
The current version is BS 7671:2008+A3:2015 (the 17th edition incorporating Amendment 3:2015) issued in 2008 and updated ("Amendment no. 3") in January 2015 and mandatory from July 2015, although some provisions only come into force in January 2016.BS 7671 is also used as a national standard by other countries, which base their wiring regulations on BS 7671.
The first edition was published in 1882 as the "Rules and Regulations for the Prevention of Fire Risks arising from Electric Lighting." The title became "General Rules recommended for Wiring for the Supply of Electrical Energy" with the third edition in 1897, "Wiring Rules" with the fifth edition of 1907, and settled at "Regulations for the Electrical Equipment of Buildings" with the eighth edition in 1924. It did not become a recognized British Standard until the publication of the 16th edition in 1992.
The standard is maintained by the Joint IET/BSI Technical Committee JPEL/64, the UK National Committee for Wiring Regulations, and published by the IET (formerly IEE). Although the IET and BSI are non-governmental organisations and the Wiring Regulations are non-statutory, they are referenced in several UK statutory instruments, and in most cases, for practical purposes, have legal force as the appropriate method of electric wiring. The BSI (British Standards Institute) publish numerous titles concerning acceptable standards of design/safety/quality across different fields.
Since the 15th edition (1981), these regulations have closely followed the corresponding international standard IEC 60364. In 1992, the IEE Wiring Regulations became British Standard BS 7671 and they are now treated similar to other British Standards. BS 7671 has converged towards (and is largely based on) the European Committee for Electrotechnical Standardization (CENELEC) harmonisation documents, and therefore is technically very similar to the current wiring regulations of other European countries.

Friday, March 11, 2016

IEC – German Standard Typical residential wiring diagram issued from VDE 0100 requirements for electrical installations

IEC – German Standard
Typical residential wiring diagram issued from VDE 0100 requirements for electrical installations.

SUPPLY
May be single phase (230 V-50 Hz) or - in the majority of cases - 3 phases (400 / 230 V-50 Hz). Max. Tolerance (voltage): + 6% / -10%. TN- and TT- systems are in use. TT- systems are the most common in domestic installations. There is usually one meter. Facilities are provided with a second meter for special tariffs, etc. A fuse isolator unit allows all phases to be cut-off, isolating the whole domestic installation.

DISTRIBUTION BOARD
The distribution board usually contains pre-fuses (for example 3 x 32 A), RCBO 30 mA for household applications (1 or 3 poles). Transformer(s) as for entry door systems, MCB (16 A for general circuits up to 32 A (3 poles) for (water) heating systems). Time lag switches in dwellings. These devices are all mounted on a DIN-Rail.

POWER CIRCUITS
Single phase up to 3 WA, 7.3 KVA: 3 phases. Electrical appliances having a high power consumption (cookers, washing machines, etc.) are supplied via a specific circuit and connected either to 16 A socket-outlet or cable outlet or to a specific socket Perilexi or CEE 17. It is not uncommon to find 3 phases appliances. Protection rating and cable size of each circuit are calculated according to the appliance (min section 1.5 mm2 Cu 16 A).

GENERAL CIRCUITS
These circuits supply both lighting points and socket outlets. The rating of the protective device is usually 16 A. There is no limitation of the number of outlets on a circuit. This limit is calculated according to expected/probable use of the circuit. Socket outlets are generally of the 2P+E type “German". These plugs are non-polarized. All German socket outlets are earthed. In general, the protective conductor is distributed throughout all circuits. For class II devices < 2.5 A, the Euro-plug is used. The wire cross-section of the fixed installed cables is normally 1.5mm² (protected by a 16 A Circuit Breaker).

DAMP & OUTDOOR
INSTALLATIONS
Special rules apply, in particular for IP rating of accessories and equipment and RCD Protection.

EARTHING
Earthing is local, usually through a foundation earthing arrangement. All metallic services shall be bonded (gas and water pipe, heating, waste systems, etc.) with a 10 mm2. In bathrooms the local equipotential bonding could have a cross sectional area of 4 mm2. Neutral is re-earthed in the control panel. A protective conductor is distributed to all socket outlets.

INSTALLATION RULES
The installation must comply with the requirements of VDE 0100 and the “TAB” (TAB = technische Anschlussbedingungen = special requirements of the energy supplier, for example EON, RWE, EnBw or Wattenfall). Installations may only be erected by registered and qualified electricians.

BATHROOMS
Special rules apply to bathrooms. The room is divided into different zones:

Zone “Bereich 0”: Electrical equipment are not allowed. Only special SELV-devices, max.12V AC or max. 30V DC are allowed. The power supply for these SELV-circuits is not allowed in “Bereich 0” and in “Bereich 1”.

Zone “Bereich 1”: Only fixed installed electrical equipment for hot water production and SELV or PELV –devices (max. 25V AC or max. 60V DC) are allowed. The power supply for the SELV- or PELV -circuits has to be installed outside “Bereich 0” and in “Bereich 1”.

Zone “Bereich 2”: Only Electrical equipment supplied by SELV- or PELV (max. 25V AC or max.60V DC) are allowed. Only shaver sockets according to DIN EN 61558-2-5 are allowed. In bathrooms, an additional equipotential bonding and RCDs (30 mA) protection for socket outlets are mandatory (Details in the DIN VDE 0100-701).

HOME AND BUILDING CONTROL
KNX (EIB) ISO/IEC14543, EN50090 is common in big and luxury installations.

ACCESSORIES
They shall comply with the appropriate VDE standards. Flush accessories are fitted in boxes. Claw-mounting and screw-mounting are used.

ENERGY SAVING & REGENERATIVE POWER GENERATION
Single-room heating control and time-controlled hot water supply is mandatory due to the EnEV (energy saving directive). Airproof installations are common in low energy buildings. More and more roofs are equipped with photovoltaic cells

NEC-Standard Typical Residential Wiring Diagram and Electrical Installation Requirements from NEC

NEC-Standard
Typical Residential Wiring Diagram and Electrical Installation Requirements from NEC



SUPPLY
Domestic supply is usually 2 phases (120 V/240 V - 60 Hz). 2 phases + neutral are supplied. Neutral is re-earthed at entry. Earth is local.

METER
Usually a weatherproof unit outside the house.

SERVICE PANEL
Ratings of 60 A, 100 A, 150 A and 200 A exist. The Service Panel (or Service Entrance Panel) usually contains a Main Disconnect device and the necessary protective devices for the sub-circuits.

POWER CIRCUITS
Appliances having heavy power consumption (ranges, water-heaters, etc.) are supplied on a specific circuit, often 120/240 V. Various socket outlets of appropriate ratings are available, these are noninterchangeable, thus 2 Phase + Neutral + Earth plug cannot be fitted to a 2 Phase + Earth socket, etc.

GENERAL PURPOSE CIRCUITS
These are 120 V-15 A and supply socket outlets (IP+N+G).These circuits supply bedrooms, etc. where the use of a large number of appliances is unlikely. Note that all general purpose socket outlets must be of the grounding type.

APPLIANCE CIRCUITS
The 120 V-20 A circuits supply areas such as kitchens,dining-rooms. etc., when there is a likelihood of more intensive use of appliances. The NEC [National Electrical Code) requires at least two appliance circuits for a domestic installation.Only socket outlets may be supplied on an appliance circuit. All domestic use NEMA 5-15R and 5-20R receptacles must be tamper resistant.

PLUGS
Various types of plugs exist to match the various configurations of socket outlets.

OUTDOORS
Outdoor socket outlets must have 6 mA GFCI protection and be housed in a weatherproof enclosure.

GROUND-FAULT CIRCUITINTERRUPTERS
(GFCI)
All domestic use 125 V - 15 A and 20 A socket outlets in the following locations must be protected by GFCI having a trip level sensitivity of 6 mA:
- Bathrooms
- Garages
- Kitchens
- Basements
- Outdoors
- Laundry and utility sinks (when socket outlets are within 6 feet).

ARC-FAULT CIRCUITINTERRUPTERS
(AFCI)
All domestic use 120 V - 15 A and 20 A branch circuits supplying outlets in living rooms, dining rooms, family rooms, bedrooms and similar areas must be AFCI protected.

TAMPER RESISTANT
(SHUTTERED) SOCKET OUTLETS
All domestic use 125 V - 15 A and 20 A socket outlets must be Tamper Resistant (shuttered).

EARTHING (GROUNDING)
The use of ungrounded (2P) sockets in domestic installations is no longer allowed by the NEC. Earth can be distributed in the installation in one or two ways:
- By a specific earth conductor distributed along with live + neutral
- By using metallic boxes, conduit and sheathed cables and using this metallic system as earth.
All conductive non-current carrying parts of the electrical system should be effectively bonded to earth.

Polarity:
Polarity is conserved throughout the installation.

Live (hot):
Terminal screws brass colour; conductors insulated in black

Neutral:
Terminal screws silver or marked white or W; conductor insulated in white.

Ground:
Terminals green colour or marked G; conductors insulated in green or wire is left bare.

Cabling:
Various types of cables are used in domestic installations, the most frequent are:

NM. Non-metallic sheathed; AC, Metal-clad cable.

Similarly various types of conduits are also encountered:
- Rigid steel conduit
- Intermediate metal conduit
- Thinwall metal conduit
- Flexible metal conduit
- Rigid non-metallic conduit
- Surface raceway.

ELECTRICAL ACCESSORY
INSTALLATION
Accessories are fitted in standard boxes, either metal or plastic, the most common sizes being 2 inches by 4 inches and 4 inches by 4 inches.